Table Of ContentPlanning Instructions
MEW01776
Revision -
Fire Alarm System EBL512 G3
V2.2.x
Author: Jan Pettersson Date of issue: 2015-01-19 Date of rev:
This page has deliberately been left blank.
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
Table of contents
1 Introduction________________________________ 9
2 Definitions / Explanations ___________________ 11
2.1 PESN AB _______________________________________ 11
2.2 Alarm points _____________________________________ 11
2.2.1 Smoke detector _______________________________ 11
2.2.2 Sensor ______________________________________ 11
2.2.3 Analog detector _______________________________ 11
2.2.4 Analog Sensor Base (ASB) ______________________ 11
2.2.5 Conventional detector __________________________ 11
2.2.6 Conventional Detector Base (CDB) _______________ 11
2.2.7 Addressable __________________________________ 12
2.2.8 Conventional zone line input / External line _________ 12
2.3 Output unit ______________________________________ 12
2.4 Output / Control output _____________________________ 12
2.5 Short circuit isolator (ISO) __________________________ 12
2.6 Display unit (D.U.) ________________________________ 12
2.7 COM loop _______________________________________ 12
2.8 Control Unit / C.U. / C.I.E. __________________________ 12
2.9 Fire Brigade Panel (FBP) ___________________________ 12
2.10 Control panel (CP) ________________________________ 13
2.11 System / Installation _______________________________ 13
2.12 Network / TLON® / LonWorks® / Echelon / Node / TLON
Conn. board / Channel / Backbone net / Router / Repeater _______ 13
2.13 LED ____________________________________________ 13
2.14 External Indicator (Ext. LED) ________________________ 13
2.15 Display / LCD ____________________________________ 14
2.16 Door open (Door / Key switch) _______________________ 14
2.17 Site Specific Data (SSD) ____________________________ 14
2.18 Software (S/W) / Firmware / System program ___________ 14
2.19 EBLWin ________________________________________ 14
2.20 Web-server ______________________________________ 14
2.21 EN54-13 ________________________________________ 14
3 Overview _________________________________ 15
3.1 The EBL512 G3 system ____________________________ 15
3.1.1 Printer ______________________________________ 15
3.1.2 Expansion boards _____________________________ 15
3.1.3 Power supply _________________________________ 16
3.2 Software (S/W) versions ____________________________ 16
3.3 Documents ______________________________________ 16
3.4 Applications _____________________________________ 16
3.5 PC programs _____________________________________ 16
3.5.1 EBLWin ____________________________________ 16
1
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
3.5.2 TLON Manager _______________________________ 17
4 Control Unit / TLON Network _______________ 18
4.1 The TLON Network _______________________________ 18
4.2 Single TLON Network / Redundant TLON Network ______ 18
5 Control Units 5000 and 5001 _________________ 20
5.1 Mounting plates ___________________________________ 23
5.1.1 Mounting plate for 19" mounting rack, 5020 ________ 23
5.1.2 Mounting plate for inflammable wall, 5021 _________ 23
5.2 COM loops ______________________________________ 23
5.3 Programmable voltage outputs (S0-S3) ________________ 24
5.4 Programmable relay outputs (R0-R1) __________________ 24
5.5 Programmable inputs (I0-I3) _________________________ 24
5.6 Relay outputs for routing equipment (tx) _______________ 25
5.6.1 Fire alarm output ______________________________ 25
5.6.2 Fault condition output __________________________ 25
6 Expansion boards 458x _____________________ 26
6.1 Expansion board no. (address) setting __________________ 27
6.2 8 zones expansion board 4580 _______________________ 27
6.2.1 Type of zone line input _________________________ 28
6.2.2 Input states __________________________________ 28
6.3 8 relays expansion board 4581 _______________________ 29
6.4 Inputs and outputs expansion board 4583 _______________ 30
6.5 Inputs and outputs expansion board 4583DE ____________ 31
6.6 I/O Matrix board 4582 _____________________________ 33
6.6.1 Generic _____________________________________ 34
6.6.2 Fan control __________________________________ 34
6.6.3 Zone control _________________________________ 35
7 Printer ___________________________________ 36
7.1 EBL512 G3 ______________________________________ 36
7.2 Ext. Fire Brigade Panel 1826 ________________________ 36
8 TLON connection board 5090 ________________ 37
8.1 Single TLON Network _____________________________ 37
8.2 Redundant TLON network __________________________ 37
8.3 Network programming _____________________________ 37
9 Peripheral devices __________________________ 38
9.1 COM loop units ___________________________________ 38
9.1.1 Input units ___________________________________ 40
9.1.2 Addressable I/O units __________________________ 53
9.1.3 Alarm devices (addressable sounders) _____________ 55
9.1.4 Short circuit isolators (addressable) _______________ 57
9.1.5 Built-in isolators ______________________________ 59
9.1.6 Units for Hazardous (Ex) areas ___________________ 59
9.1.7 Other COM loop units __________________________ 60
9.1.8 Obsolete units ________________________________ 62
2
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
9.2 Units connected to the RS485 interface ________________ 62
9.2.1 External Fire Brigade Panels _____________________ 63
9.2.2 Alert Annunciation Units _______________________ 64
9.2.3 External Presentation Units ______________________ 65
9.2.4 German Fire Brigade Panels - Schraner ____________ 66
9.2.5 Swiss Fire Brigade Panel - IFAM _________________ 67
9.2.6 German Fire Brigade Panels - IFAM ______________ 68
9.3 Units connected to the RS232 interface J7 ______________ 68
9.3.1 Web-servers __________________________________ 68
9.4 Other units _______________________________________ 69
9.4.1 Alert Annunciation Controllers ___________________ 69
9.4.2 External LED ________________________________ 70
9.4.3 Alarm devices (sounders, etc.) ___________________ 70
9.4.4 Door release magnets __________________________ 70
9.4.5 Boxes _______________________________________ 71
9.4.6 Duct detector chambers _________________________ 71
9.4.7 German key cabinet ____________________________ 71
10 Programmable inputs _______________________ 72
10.1 Control unit Inputs I0 - I3 ___________________________ 72
10.2 Inputs 0 - 4 on exp. board 4583 _______________________ 72
10.2.1 Not supervised ________________________________ 72
10.2.2 Supervised ___________________________________ 72
10.3 Inputs 0 - 4 on exp. board 4583DE ____________________ 73
10.3.1 Not supervised ________________________________ 73
10.3.2 Supervised ___________________________________ 73
10.4 The 3361 unit's Inputs In0 / Z & In1 ___________________ 74
10.4.1 Input In0 ____________________________________ 74
10.4.2 Input In1 ____________________________________ 74
11 Input programming ________________________ 75
11.1 Trigger conditions _________________________________ 75
11.2 Logic ___________________________________________ 78
11.2.1 Supervised ___________________________________ 79
12 Programmable outputs ______________________ 80
12.1 Control unit outputs S0 – S3 _________________________ 81
12.2 Control unit outputs R0 & R1 ________________________ 82
12.3 8 relays expansion board 4581 Output 0 – Output 7 _______ 82
12.4 Inputs and Outputs expansion board 4583 Output 0 & Output 182
12.5 Inputs and Outputs expansion board 4583DE Output 0 &
Output 1 _______________________________________________ 82
12.6 The 3361 unit's Outputs Re0 & Re1 ___________________ 83
12.7 The 3364 unit's VO0 – VO2 _________________________ 83
12.8 The 3377 / 4477 unit's Output (siren) __________________ 83
12.9 The 3379 unit's Output (sounder) _____________________ 84
12.10 The 4380 unit's Output (beacon) ____________________ 84
12.11 The 4383 unit's Output (light) ______________________ 84
3
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
12.12 The 4611 wireless smoke detector Output (sounder) ____ 84
13 Output programming _______________________ 85
13.1 Type of output ____________________________________ 85
13.2 Logic ___________________________________________ 86
13.3 Supervised / Not supervised _________________________ 86
13.4 Output signal period _______________________________ 86
13.5 Control expression ________________________________ 89
13.5.1 Trigger conditions _____________________________ 89
13.5.2 Logical operators ______________________________ 96
13.5.3 Control expression examples ____________________ 96
14 Short circuit isolators ______________________ 101
15 Interlocking function ______________________ 104
15.1 Programming of interlocking function ________________ 104
15.1.1 Interlocking output ___________________________ 104
15.1.2 Interlocking input ____________________________ 104
15.1.3 Interlocking combination ______________________ 104
15.2 Interlocking indications ____________________________ 106
15.3 Interlocking outputs and inputs (H9) _________________ 106
15.3.1 Activated interlocking outputs / inputs (H9/C1) _____ 106
15.3.2 Activate / deactivate interlocking output (H9/C2) ___ 107
15.3.3 Disable / re-enable interlocking output (H9/C3) _____ 107
15.4 Interlocking control expressions _____________________ 107
16 Fire Door Closing _________________________ 108
17 Functions / Services / Features ______________ 109
17.1 Sensor value ____________________________________ 109
17.2 Week average sensor value _________________________ 109
17.3 Decision value ___________________________________ 110
17.4 Alarm algorithms for smoke detectors / Detection levels /
Offsets 110
17.4.1 Alarm algorithm / Alternative alarm algorithm _____ 111
17.4.2 Filtering algorithm ___________________________ 112
17.4.3 Smouldering smoke algorithm __________________ 114
17.4.4 Performance factor ___________________________ 115
17.5 Algorithms for analog heat detectors _________________ 116
17.5.1 Class A1 algorithm ___________________________ 116
17.5.2 Class A2 S algorithm _________________________ 117
17.5.3 Class B S algorithm ___________________________ 117
17.6 Self verification __________________________________ 117
17.7 Minimum / Maximum sensor values __________________ 118
17.8 2-zone / 2-address dependence (Co-incidence alarm) _____ 119
17.8.1 2-zone dependence ___________________________ 119
17.8.2 2-address (-unit) dependence ___________________ 120
17.8.3 Reset of 2-zone / 2-address dependence (co-incidence
alarm 120
17.9 Delayed alarm ___________________________________ 121
4
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
17.10 Selective Alarm Presentation _____________________ 121
17.11 Alarm Verification Facility _______________________ 121
17.12 Alert Annunciation _____________________________ 122
17.13 Local Alarm Acknowledgement (LAA) _____________ 124
17.14 Quiet alarm ___________________________________ 126
17.15 Fire alarm type A and Fire alarm type B _____________ 126
17.15.1 Fire alarm type B ___________________________ 127
17.15.2 Fire alarm type A __________________________ 127
17.16 Disable alarm points and outputs __________________ 127
17.16.1 Disable zone ______________________________ 128
17.16.2 Disable zone / address _______________________ 128
17.16.3 Disable control output _______________________ 128
17.16.4 Disable / Re-enable output type _______________ 128
17.16.5 Disable / Re-enable alarm devices _____________ 128
17.17 Disable interlocking output _______________________ 129
17.18 Disable outputs for routing equipment ______________ 129
17.19 Disconnect & Re-connect loop / zone line input _______ 129
17.20 External time channels __________________________ 129
17.21 Test mode ____________________________________ 129
17.22 Test alarm devices ______________________________ 130
17.23 Test of outputs _________________________________ 130
17.24 Test of routing equipment ________________________ 130
17.25 Calibration of supervised outputs __________________ 131
17.26 Service signal _________________________________ 131
17.27 Fault signal (fault condition) ______________________ 131
17.28 Alarm texts ___________________________________ 132
17.28.1 Creating the alarm texts via EBLWin ___________ 132
17.28.2 Downloading alarm texts to the DU:s 1728 / 1735 /
1736 and ext. FBP:s 1826 / 1828 ________________________ 134
17.29 Real time clock (RTC) __________________________ 134
17.29.1 Daylight saving time ________________________ 134
17.30 Loss of main power source _______________________ 135
17.30.1 Fault: Loss of main power source ______________ 135
17.30.2 LCD backlight _____________________________ 135
17.31 Evacuate _____________________________________ 135
17.32 Zone groups ___________________________________ 135
18 Special New Zealand functions ______________ 137
19 Advanced mode ___________________________ 138
19.1 Pulse up – down counter ___________________________ 139
19.1.1 Pulse up – down counter for smoke ______________ 139
19.1.2 Pulse up – down counter for temperature __________ 140
19.1.3 Pulse up – down counter for smoke & temperature __ 140
19.2 Fire judgement __________________________________ 140
19.3 Alarm threshold levels ____________________________ 140
19.4 Alarm delay time _________________________________ 141
5
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
19.5 Learning function / Learning period __________________ 142
19.5.1 Area Alarm algorithms ________________________ 142
19.6 Analog data output _______________________________ 144
19.7 Sensitivity compensation __________________________ 144
19.8 Self diagnosis of internal devices ____________________ 145
19.9 Address setting check _____________________________ 145
19.10 Polling LED __________________________________ 145
20 Control unit properties ____________________ 146
20.1 Control unit properties dialog box ___________________ 146
20.1.1 General Information __________________________ 146
20.1.2 Peripherals __________________________________ 146
20.1.3 Misc. ______________________________________ 146
20.2 EBLWin Control unit pop-up menu __________________ 147
20.2.1 Reset alarm counter ___________________________ 147
20.2.2 Software version _____________________________ 148
20.2.3 Upgrade number of alarm points _________________ 148
20.2.4 Show event log ______________________________ 148
20.2.5 Restart _____________________________________ 149
20.2.6 Delete _____________________________________ 149
20.2.7 Properties___________________________________ 149
20.2.8 Add Web-server _____________________________ 149
21 System properties (settings) _________________ 150
21.1 System properties dialog box _______________________ 150
21.1.1 Name ______________________________________ 150
21.1.2 User definable text ___________________________ 150
21.1.3 System properties, Page 1 ______________________ 150
21.1.4 System properties, Page 2 ______________________ 152
22 EBLWin menus ___________________________ 154
22.1 The File menu ___________________________________ 154
22.1.1 New _______________________________________ 154
22.1.2 Open ______________________________________ 154
22.1.3 Import from Win512 __________________________ 154
22.1.4 Report _____________________________________ 154
22.1.5 Save _______________________________________ 155
22.1.6 Save As ____________________________________ 155
22.1.7 Print labels __________________________________ 155
22.2 The View menu __________________________________ 155
22.2.1 Tree view ___________________________________ 155
22.2.2 Deviations __________________________________ 156
22.2.3 Selected loop ________________________________ 156
22.2.4 Alarm points ________________________________ 156
22.2.5 Interlocking combinations ______________________ 157
22.2.6 External faults _______________________________ 157
22.2.7 Technical warnings ___________________________ 157
22.2.8 External time channels ________________________ 158
6
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
22.3 The System menu ________________________________ 158
22.3.1 Properties___________________________________ 158
22.3.2 Time channels _______________________________ 158
22.3.3 Alarm algorithms ____________________________ 160
22.3.4 Output Signal Periods _________________________ 162
22.3.5 National holidays ____________________________ 163
22.3.6 Two zone dependence _________________________ 164
22.3.7 Zone groups _________________________________ 165
22.3.8 System information ___________________________ 166
22.3.9 Edit Alarm texts _____________________________ 166
22.3.10 User data _________________________________ 166
22.4 The Tools menu__________________________________ 168
22.4.1 Web-server _________________________________ 169
23 Download SSD ____________________________ 171
23.1 COM loop menu _________________________________ 172
23.1.1 Check Loop _________________________________ 172
23.1.2 Auto generate loop ___________________________ 172
23.2 Single Control Unit _______________________________ 173
23.3 Control Units in a TLON network ___________________ 173
23.4 User definable text messages download _______________ 173
24 Download software (S/W) __________________ 174
24.1 Single control unit (c.i.e.) __________________________ 174
24.2 Control Units in a TLON network ___________________ 176
25 Compatibility_____________________________ 177
26 Cable types ______________________________ 178
26.1 TLON Network cables ____________________________ 178
26.2 COM loop cables_________________________________ 178
26.3 Ext. FBP / Display Units cables _____________________ 178
26.4 Conventional zone line cables _______________________ 178
26.5 Alarm device cables ______________________________ 179
26.6 Other cables _____________________________________ 179
27 COM loop cable length _____________________ 180
28 Current consumption ______________________ 183
29 Power supply _____________________________ 188
29.1 Charger functions ________________________________ 189
29.1.1 Charging ___________________________________ 189
29.1.2 Battery charging functions: _____________________ 189
29.1.3 Security functions ____________________________ 189
29.2 Current consumption calculations ____________________ 190
29.3 Power supply (rectifier) - main power source ___________ 191
29.4 Battery - second power source ______________________ 191
29.5 Fuses __________________________________________ 192
29.6 Form / Table of current consumption _________________ 193
30 S/W versions _____________________________ 194
7
Panasonic Eco Solutions Nordic AB
MEW01776 Rev: - Planning Instructions Fire alarm system EBL512 G3, V2.2.x
31 Technical data ____________________________ 195
32 Limitations_______________________________ 196
32.1 User definable texts _______________________________ 196
32.2 C.i.e. / System ___________________________________ 196
33 National regulations _______________________ 198
34 Drawings / connection diagrams _____________ 199
35 Revision history ___________________________ 200
Drawings according to the valid table of drawings.
8
Description:units. The TLON Network makes it possible to install the control units in one building or in different buildings. 3.5. PC programs. The following PC programs are used together with the EBL512 G3 system. 3.5.1. EBLWin. The PC program EBLWin is used for programming and commissioning of one or